These are keywords that apply to Hardware specifications TC16:
.
For more information, please content info@telecontrolsystems.eu
Go to Content.


Hardware specifications TC16 -





Home
Telecontroller
Software
Applications
News
Company
Support
Partners
Contact




Telecontrol Systems

Hardware specificaties TC16


TC16 without display and push buttons

TC16 with display and push buttons (in option)

Digital inputs 16 (24 V DC)
Sampling of digital inputs First 4 inputs 500Hz, the other inputs 20Hz
Digital outputs 8 (relays, 5...230V/2,5A)
Recommended temperature 0 up to +50°C (32 up to 122 F)
Up to 95% relative humidity
Size (mm) 217 x 140 x 66
Weight (in grams) 866
Housing RVS
standard: IP20
on request: up to IP68
Mounting DIN-rail
Cabling Removable screw connection
EMC EN 50082-2 and EN 50081-1 in heavy industrial environment
Real Time Clock yes
Consumption 80mA at 24 V DC
+7mA per active input
+10mA per active output
PSTN-Modem External
GSM/GPRS-modem (dual band) External
RS232/RS485-port 1 RS232/RS485-port
Supply 24 V DC
Supply 230 V AC Optional, external
Battery/Battery charger Optional, external
Adapter for 12 V DC in Optional, external
LCD-display/push buttons Yes, optional
LEDs - 16 + 8 (digital inputs and outputs)
- 2 LEDs status
- 3 LEDs communication activity
Available memory for the user program 192 Kbyte Flash and 64 Kbyte RAM data memory with battery back-up
Datalog memory 384 Kbyte RAM, expandable to 1,92 Mb RAM with battery back-up
Modbus-RTU yes
C-programmable yes
Built-in TCP/IP-stack and mini webserver yes
Alarm management yes
Sending alarms/data via FTP/XML, Semascript yes

Internal expansions

Number of possible internal expansions 1
Possible internal expansions:
Analog inputs (12 bit resolution) / Analog outputs (10 bit resolution)

4 analog inputs (0...5V/0...10V/0..20mA) + 2 analog voltage outputs (0...10V) yes
8 analog inputs (0...5V/0...10V/0..20mA) + 4 analog voltage outputs (0...10V) yes
2 analog inputs (0...10V) + 4 analog current outputs (0...20mA) yes
8 analog inputs (0...20mA) + 4 analog current outputs (0...20mA) yes

18 digital inputs, RS232-communication port with a higher communication speed yes

1x PT100 + 2x analog input (0...10V) + RS422 + 6 transistor outputs + 1 pressure sensor (0...100 mbar, resolution 0.03 mbar) yes

2x PT100 + 3 analog inputs (0...10V) + 1 analog input (0...20mA) + 1 analog output (0...10V) + RS485 + 6 transistor outputs yes

External expansions

Number of possible external expansions up to 3 slots
Digital input and output cards
16 inputs 24 V DC among which 4 fast inputs (500Hz) yes
32 inputs 24 V DC yes
8 outputs (relay) max. 24 V AC yes
8 outputs (transistor) 24V/0,8A/NPN yes
16 outputs (transistor) 24V/0,5A,not protected against possible short-circuit, PNP yes
8 outputs (relay) max. 24 V AC with flatcable connector (26 poles) yes
16 outputs (relay) max. 24 V AC yes
Analog input and output cards
6 channels analog-in 0-1V/0-10V/ 0...20mA, 12 bit resolution, 0,5% precision, seperated galvanically with max. 4 conditioning modules PT100/PT1000(option) yes
2 channels analog output card 0-10V DC, 8 bit resolution, seperated galvanically yes
Communication and network cards
2 channels RS232-communication card, with 2 DB9 connectors, communication speed up to 19200 bd. yes
1 channel RS485-communication card with DB9 connector, seperated galvanically. yes
2 channels RS232-communication card, with 2 DB9 connectors. Higher communication speed resulting from lower weight on CPU (38400 bd). yes
10 Mbit Ethernet network card with twisted pair connection. yes
MDB-communication card (master/slave) yes
V-netŪ (ARC-net protocol) yes
Profibus Master module yes
Profibus Slave module yes
Can-Open Master module yes
Can-open Slave module yes

Remark

Ultra Low Power version (ULP) Yes, optional